Thermocouple Type
A thermocouple is a sensor for measuring temperature. It consists of two dissimilar metals, joined together at one end. When the junction of the two metals is heated or cooled a voltage is produced that can be correlated back to the temperature. The thermocouple alloys are commonly available as wire.
Available Thermocouple Types
A thermocouple is available in different combinations of metals or calibrations. The four most common calibrations are J, K, T and E. There are high temperature calibrations R, S, C and GB. Each calibration has a different temperature range and environment, although the maximum temperature varies with the diameter of the wire used in the thermocouple. Although the thermocouple calibration dictates the temperature range, the maximum range is also limited by the diameter of the thermocouple wire. That is, a very thin thermocouple may not reach the full temperature range. Click here to view a complete reference table for each thermocouple. The table includes international color codes for thermocouple alloys, temperature range and limits of error for almost every kind of thermocouple.
Selecting Your Thermocouple Type
Because a thermocouple measures in wide temperature ranges and can be relatively rugged, thermocouples are very often used in industry. The following criteria are used in selecting a thermocouple:
Temperature range
Chemical resistance of the thermocouple or sheath material
Abrasion and vibration resistance
Installation requirements (may need to be compatible with existing equipment; existing holes may determine probe diameter)
Selecting Your Thermocouple Junction
Sheathed thermocouple probes are available with one of three junction types: grounded, ungrounded or exposed (see graphic below:"Thermocouple Tip Styles"). At the tip of a grounded junction probe, the thermocouple wires are physically attached to the inside of the probe wall. This results in good heat transfer from the outside, through the probe wall to the thermocouple junction. In an ungrounded probe, the thermocouple junction is detached from the probe wall. Response time is slower than the grounded style, but the ungrounded offers electrical isolation (see table below).
Type K Thermocouple
Type K (chromel{90 percent nickel and 10 percent chromium}–alumel) (Alumel consisting of 95% nickel, 2% manganese, 2% aluminium and 1% silicon) is the most common general purpose thermocouple with a sensitivity of approximately 41 µV/°C, chromel positive relative to alumel. It is inexpensive, and a wide variety of probes are available in its −200 °C to +1350 °C / -328 °F to +2462 °F range. Type K was specified at a time when metallurgy was less advanced than it is today, and consequently characteristics vary considerably between samples. One of the constituent metals, nickel is magnetic; a characteristic of thermocouples made with magnetic material is that they undergo a step change in output when the magnetic material reaches its curie point (around 354 °C for type K thermocouples).
Type E Thermocouple
Type E (chromel–constantan)has a high output (68 µV/°C) which makes it well suited to cryogenic use. Additionally, it is non-magnetic.
Type J Thermocouple
Type J (iron–constantan) has a more restricted range than type K (−40 to +750 °C), but higher sensitivity of about 55 µV/°C. The Curie point of the iron (770 °C) causes an abrupt change in the characteristic, which determines the upper temperature limit.
Type N Thermocouple
Type N (Nicrosil–Nisil) (Nickel-Chromium-Silicon/Nickel-Silicon) thermocouples are suitable for use at high temperatures, exceeding 1200 °C, due to their stability and ability to resist high temperature oxidation. Sensitivity is about 39 µV/°C at 900 °C, slightly lower than type K. Designed to be an improved type K, it is becoming more popular.
Platinum types B, R, and S
Types B, R, and S thermocouples use platinum or a platinum–rhodium alloy for each conductor. These are among the most stable thermocouples, but have lower sensitivity than other types, approximately 10 °C. Type B, R, and S thermocouples are usually used only for high temperature measurements due to their high cost and low sensitivity.
Type B Thermocouple
- Type B thermocouples use a platinum–rhodium alloy for each conductor. One conductor contains 30% rhodium while the other conductor contains 6% rhodium. These thermocouples are suited for use at up to 1800 °C. Type B thermocouples produce the same output at 0 °C and 42 °C, limiting their use below about 50 °C.
Type R Thermocouple
Type R thermocouples use a platinum–rhodium alloy containing 13% rhodium for one conductor and pure platinum for the other conductor. Type R thermocouples are used up to 1600 °C.
Type S Thermocouple
Type S thermocouples are constructed using one wire of 90% Platinum and 10% Rhodium (the positive or "+" wire) and a second wire of 100% platinum
(the negative or "-" wire). Like type R, type S thermocouples are used up to 1600 °C. In particular, type S is used as the standard of calibration for the melting point of gold (1064.43 °C).
Type T Thermocouple
Type T (copper–constantan) thermocouples are suited for measurements in the −200 to 350 °C range. Often used as a differential measurement since only copper wire touches the probes. Since both conductors are non-magnetic, there is no Curie point and thus no abrupt change in characteristics. Type T thermocouples have a sensitivity of about 43 °C.
Type C Thermocouple
Type C (tungsten 5% rhenium– tungsten 26% rhenium) thermocouples are suited for measurements in the 0 °C to 2320 °C range. This thermocouple is well-suited for vacuum furnaces at extremely high temperatures. It must never be used in the presence of oxygen at temperatures above 260 °C.
Type M Thermocouple
Type M thermocouples use a nickel alloy for each wire. The positive wire contains 18% molybendum while the negative wire contains 0.8% cobalt. These thermocouples are used in vacuum furnaces for the same reasons as with type C. Upper temperature is limited to 1400 °C. It is less commonly used than other types.
Chromel-Gold/Iron
- In chromel-gold/Iron thermocouples, the positive wire is chromel and the negative wire is gold with a small fraction (0.03–0.15 atom percent) of iron. It can be used for cryogenic applications (1.2–300 K and even up to 600 K). Both the sensitivity and the temperature range depends on the iron concentration. The sensitivity is typically around 15 µV/K at low temperatures and the lowest usable temperature varies between 1.2 and 4.2 K.